Carrier Weathermaker 8000 Manual Download

  1. Carrier Weathermaker 8000 Manual Reset
  2. Carrier Weathermaker 8000 Problems
  3. Carrier Weathermaker 8000 Manual Download Windows 7
  4. Carrier Weathermaker 8000 Manual Download Pdf
  5. Carrier Weathermaker 8000 Service Manual
  6. Carrier Weathermaker 8000 Manual Download Free

View and Download Carrier WeatherMaker 8000 product data online. WeatherMaker 8000 Furnace pdf manual download. Service and Maintenance Instructions For Sizes 040-140, Series 160 ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death, or property dam-age. Improper servicing could result in dangerous operation, serious injury, death, or property damage.

Gas Heating / Electric Cooling with Puron® (R-410A) Refrigerant 20 to 60 Nominal Tons. 48A2 – CV/SAV, Vertical 48A3 - VAV, Vertical 48A4 – CV/SAV, Horizontal 48A5 - VAV, Horizontal. Carrier A Series Rooftop products are pre-wired and charged with refrigerant and tested in. View and Download Carrier Weathermaker 8000VS manual online. INDUCED-COMBUSTION GAS FURNACE. Weathermaker 8000VS Furnace pdf manual download. Also for: Weathermaker 8000ts, Weathermate 58sta, Weathermaker 8000, Weathermate 8000ts. View and Download Carrier WEATHERMAKER 8000 58WAV installation and operating instructions manual online. Induced-Combustion Furnaces Sizes 045-155, Series 110. WEATHERMAKER 8000 58WAV Furnace pdf manual download. Also for: Weathermaker 8000. Carrier WEATHERMAKER 8000 58ZAV. User guide. Download PDF for free and without registration! Manuals Directory ManualsDir.com - online owner manuals library Search.

Advertising

If coil assembly CD5, CK5, or Coil Box KCAKC is used,
install as shown in Fig. 7.

Step 6—Horizontal Attic Installation

Do not install the furnace on its back; safety control operation
will be adversely affected. Never connect return-air ducts to
the sides or back of the furnace. Failure to follow this warning
could result in fire, personal injury, or death.

The furnace can be installed horizontally on either the left-hand
(LH) or right-hand (RH) side. A typical attic installation is shown
in Fig. 8.
CONSTRUCT A WORKING PLATFORM
Construct working platform on location where all required furnace
clearances are met. (See Fig. 2 and 8.)
INSTALL FURNACE

1. Position furnace in desired location.
2. Connect gas supply pipe. See Fig. 8 for typical piping entry.
3. Install field-supplied filter retainers as indicated in Fig. 11 and

Table 4 before connecting return-air duct to furnace.

4. Connect supply- and return-air ducts.
5. Install 24- X 24-in. sheet metal shield on platform in front of

louvered control panel as shown in Fig. 8.

Step 7—Horizontal Crawlspace Installation
The furnace can be installed horizontally with either the LH or RH
side up. In a crawlspace, furnace can either be hung from floor
joist (see Fig. 10) or installed on suitable blocks or pad. (See Fig.
9.) The furnace can be suspended from each corner by hanger bolts
(4 each 3/8-in. all-thread rod) cut to desired length, 1- X 3/8-in. flat
washer, 3/8-in. lockwasher, and 3/8-in. nut. Dimples are provided
for hole locations. (See Fig. 1.)

Since horizontal crawlspace installation is very similar to attic
installation, refer to Step 6. The installation of a sheet metal shield
in front of louvered control panel is covered in Step 6. For a
crawlspace installation, this same sheet metal shield must be
installed above louvered control panel. Extend sheet metal shield
over furnace top far enough to cover gas pipe entry hole.
Step 8—Filter Arrangement

Never operate unit without a filter or with filter access door
removed. Failure to follow this warning could result in fire,
personal injury, or death.

The 2 factory-supplied filters are shipped in the blower compart-
ment. After return-air duct has been connected to furnace, install
filters in a V-formation inside return-air plenum. See Fig. 11 and

Table 4 for horizontal applications. Horizontal filter retainers must
be field supplied. See Fig. 12 for downflow applications.

Step 9—Gas Piping
Gas piping must be installed in accordance with national and local
codes. Refer to the current edition of the NFGC.
Canadian installations must be installed in accordance with NSC-
NGPIC and all authorities having jurisdiction.
Refer to Table 5 for recommended gas pipe sizing. Risers should
be used to connect to the furnace and to the meter.

If a flexible connector is required or allowed by the authority
having jurisdiction, black iron pipe shall be installed at the
gas valve and extend a minimum of 2 in. outside the furnace
casing.

Use the proper length of pipes to avoid stress on the gas
control manifold. Failure to follow this warning could result
in a gas leak, causing fire, explosion, personal injury, or
death.

Connect the gas pipe to the furnace using a backup wrench to
avoid damaging gas controls.

Carrier weathermaker 8000 troubleshooting

Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition to check
for gas leakage. Use a soap-and-water solution to check for
gas leaks. Failure to follow this warning could result in fire,
explosion, personal injury, or death.

Joint compounds (pipe dope) should be applied sparingly and only
to the male threads of the joints. This pipe dope must be resistant
to the action of propane gas.
An accessible manual shutoff valve MUST be installed upstream
of the furnace gas controls and within 72 in. of the furnace. A
1/8-in. NPT plugged tapping, accessible for test gage connection,
MUST be installed immediately upstream of the gas supply
connection to the furnace and downstream of the manual shutoff
valve. Place a ground joint union between the gas control manifold
and the manual shutoff.
Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading from the
furnace. Connect a capped nipple into the lower end of the tee. The
capped nipple should extend below the level of the gas controls.
(See Fig. 13.)
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
before the pressure test. If the test pressure is equal to or less than
0.5 psig (14-in. wc), turn off electric shutoff switch located on the
gas valve before the test. It is recommended that the ground joint
union be loosened before pressure testing.
After all connections have been made, purge the lines and check
for gas leakage with regulated gas supply pressure.

Fig. 9—Horizontal Installation on Blocks

A95235

9

Advertising
Popular Brands
Popular manuals
Advertising

Step 3—Supply Air Connections
DOWNFLOW FURNACES
Connect supply-air duct to supply-air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil casing (when used), when
installed on non-combustible material. When installed on combus-
tible material, supply-air duct attachment must ONLY be con-
nected to an accessory subbase or factory approved air condition-
ing coil casing. DO NOT cut main furnace casing to attach supply
side air duct, humidifier, or other accessories. All accessories
MUST be connected external to furnace main casing.
HORIZONTAL FURNACES
Connect supply-air duct to supply air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace

supply/outlet or air conditioning coil casing (when used). DO NOT
cut main furnace casing to attach supply side air duct, humidifier,
or other accessories. All accessories MUST be connected external
to furnace main casing.
Step 4—Return Air Connections
The return-air duct must be connected to return-air opening
provided as shown in Fig. 1. DO NOT cut into casing sides or back
to attach any portion of return-air duct. Bypass humidifier connec-
tions should be made at ductwork or coil casing sides exterior to
furnace.

Fig. 3—Confined Space: Air for Combustion and

Kia optima gs4 download unsuccessful android. Ventilation from an Unconfined Indoor Space

A93387

RETURN

AIR

6″ MIN

(FRONT)

SUPPLY AIR

VENT THROUGH ROOF

(CATEGORY I)

1 SQ IN.

PER 1000

BTUH* IN DOOR

OR WALL

12″ MAX

1 SQ IN.

PER 1000

BTUH* IN DOOR

OR WALL

12″ MAX

INTERIOR

HEATED

SPACE

* Minimum opening size is 100 sq in. with

minimum dimensions of 3 in.

Minimum of 3 in. when type B-1 vent is used.

UNCONFINED

SPACE

Fig. 4—Confined Space: Air for Combustion and

Ventilation from Outdoors

A93388

DUCTS TO

OUTDOORS

1 SQ IN.

PER 4000

BTUH

*

RETURN

AIR

VENT

THROUGH

ROOF

(CATEGORY I)

D

Carrier Weathermaker 8000 Manual Reset

B

A

C

E

1 SQ IN.

PER 4000

BTUH

DUCT

TO

OUTDOORS

SUPPLY AIR

1 SQ IN.

PER 2000

BTUH*

DUCTS

TO

OUTSIDE

12″ MAX

12″ MAX

CONFINED

SPACE

12″

MAX

12″

MAX

1 SQ IN.

PER 4000

BTUH

*

OUTDOORS

1 SQ IN.

PER 4000

BTUH

*

1 SQ IN.

PER 2000

BTUH*

12″ MAX

Use any of the following

combinations of openings:

A & B C & D D & E F & G

NOTE:

*Minimum dimensions of 3 in.

F

G

Table 2—Minimum Free Area Of Combustion Air Opening

58ZAV

FURNACE

INPUT

(BTUH)

AIR FROM UNCON-

FINED INDOOR

SPACE

OUTDOOR AIR THROUGH

VERTICAL DUCTS

OUTDOOR AIR THROUGH

HORIZONTAL DUCTS

OUTDOOR AIR THROUGH

SINGLE DUCT

Free Area

of Opening

(Sq In.)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

46,000

100

11.50

4

Carrier Weathermaker 8000 Problems

23.0

6

15.33

5

69,000

100

17.25

5

34.5

7

23.00

6

92,000

Carrier Weathermaker 8000 Manual Download Windows 7

100

23.00

6

Carrier Weathermaker 8000 Manual Download Pdf

46.0

8

30.67

7

115,000

115

28.75

7

57.5

9

38.33

7

135,000

135

33.75

7

67.5

10

45.00

8

* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances

in the space require combustion air.

6

Advertising

Carrier Weathermaker 8000 Service Manual

Popular Brands

Carrier Weathermaker 8000 Manual Download Free

Popular manuals